0.6/1kv Xlpe Insulated Power Cable
Description
0.6/1kV XLPE Insulated Power Cable |
一、Standards The cable meets the standard requirements of GB/T12706-2002 or IEC60502-1997. It is suitable to be installed in the power line with rated voltage of 0.6/1kV U0/U (Um). 二、Type, Designation and Applications Type | Designation | Applications | YJV YJLV | Cu or Al conductor XLPE insulated PVC sheathed power cable | For laying indoors, in tunnel and in ducts. Able to bear certain traction during laying but not external mechanical forces. Impermissible to lay single core cable in magnetic ducts. | YJV22 YJLV22 | Cu or Al conductor XLPE insulated PVC sheathed internal steel tape armored power cable. | For laying indoors, in tunnels, in ducts and underground. Able to bear external mechanical force but not large pulling forces. Impermissible to use single cable in A.C. circuit. | 三、Specifications Type | Number of cores | Nominal Cross-sectional Area(mm2) | YJV YJLV | 1 | 1.0~630 | YJV YJV22 YJLV YJLV22 | 2 | 1.0~400 | YJV YJV22 YJLV YJLV22 | 3 | 1.0~400 | YJV YJV22 YJLV YJLV22 | 3+1 | 4.0~400 | YJV YJV22 YJLV YJLV22 | 4 | 1.0~400 | YJV YJV22 YJLV YJLV22 | 5 | 1.0~400 | 四、Structure Drawing 五、Using properties 1.The maximum rated temperature The maximum operating temperature of cores shall not exceed 90℃ when the cable is used for long period. The temperature of cores shall not exceed 250℃ at short circuit for 5 seconds. 2、The installation of cables is not limited by the difference of level along the route. The ambient temperature should not be below 0℃ during installation. The permissible bending radius for cable shall not be less than 10 times of the cable diameter. The single cable shall be without amour or with steel wire amour when it is electrified with alternating current and shall not be laid in magnetic ducts. 六、Technical specifications Rated voltage of cable | 0.6/1kV | D.C. resistance of core | According to GB/T3856-1997 or IEC228A-82 | Power frequency withstand voltage test for 5 minutes(KV) | No breakdown at 3.5kV | Hot set test for insulation, 200℃ 15min with pressure 20N/cm2 | | Maximum elongation values at load | 175% | Maximum permanent elongation values after being cooled | 15% | Power frequency withstand voltage test for 4 hours, not break down | 2.4 | 七、Technical parameters YJV, YJLV 0.6/1kV |
|
-
Bussiness Type:
Manufacturer
Year Established:
2003
-
Main Markets:
Whole World
-
Product Focus:
Cable,Aaac Cable,Abc Cable,
|